Description of Functions and Operation SiBE811001EB31 CONVENI-PACK4. Description of Functions and Operation4.1 Operating ModeThe fundamental mode of this system differs significantly between [Air conditioning (∗1) load]and [Refrigerating (∗2) load]. The compressor operation and status of outdoor unit heatexchanger for each mode are as follows:∗1. Air conditioning is defined as [Cooling] or [Heating].∗2. Refrigerating is defined as [Refrigeration] or [Freezing].{: Compressor operation —: No operation∗3. STD compressor 1 operates alternatively when INV. compressor is on standby or duringstop for an abnormal stop situation.∗4. STD compressor 2 operates alternatively when the STD compressor 1 is on standby orduring an abnormal stop.ModePartsCoolingonlyRefrigerationonlyCooling+RefrigerationCooling∨RefrigerationCooling∧RefrigerationHeatingonlyHeating+RefrigerationHeating∨RefrigerationHeating∧Refrigeration100%HeatrecoveryHeatingsurplusINV. Compressor (∗3) — {Refrigeration {Refrigeration {Refrigeration {Refrigeration — {Refrigeration {Refrigeration {Refrigeration {Refrigeration {RefrigerationSTD Compressor 1 (∗4) {Airconditioning({)Loadsfluctuate{Airconditioning{Airconditioning{Refrigeration{Airconditioning{Airconditioning{Airconditioning{Refrigeration({)Refrigerationloadsfluctuate({)RefrigerationloadsfluctuateSTD Compressor 2 ({)Loadsfluctuate — —{Airconditioning{Airconditioning({)Loadsfluctuate —{Airconditioning{Airconditioning — —Outdoor unit heatexchanger Condenser Condenser Condenser Condenser Condenser Evaporator Evaporator Evaporator Evaporator — CondenserAir conditioningindoor unitRefrigerationFreezerY1RY3E Y4EY6S Y1SY1EY2EY2EY1EY5EY2RHPS HPSCLRS1HPSHPSRCINV.: High pressure: Low pressure 1 (0.3~1.0MPa): Low pressure 2 (0.03~0.3MPa)INV. STD1 STD2