Troubleshooting SiBE811001EB307 CONVENI-PACK8.7 Troubleshooting by RAM Monitor (Booster Unit)Using the RAM monitor makes it possible to check the following operating data.[Main][Mode][outdoor_unit_data][Sensor]SP_No. SP numberVer. Version of softwareoperation_SW Operating switch ON/OFF (OFF/ON: 0/1)thermostat_SW Refrigerating thermostat input (AC input) ON/OFF (OFF/ON: 0/1)Mode ON/OFF: 1/0Next_mode Next operating mode to be transitionedBefore_mode Operating mode prior to current operating modeMode_complete Flag for the completion of mode change-over (incomplete/complete: 0/1)Bu_thermostat_ON Bu thermostat condition (ON/OFF: 1/0)outdoor_unit_thermostat_ON Outdoor thermostat condition transmitted from the outside (Comp condition) (ON/OFF: 1/0)Bu_driving_permission Displaying the Bu operating permission transmitted from the outside (0/1)LP1 (outdoor_unit) Low pressure sensor value of the outdoor unit transmitted from the outdoor unit (20 sec.intervals)Td1 R31T Discharge pipe temperature thermistor valueLP SINPL Low pressure sensor valueTg R6T Double tube heat exchanger inlet thermistorHP_prediction — Predicted HPTeg — Evaporating temperatureTI R4T Plate type heat exchanger outlet thermistor