Si34-603 Field SettingTest Operation 89BRC7C TypeBRC7E TypeBRC4C Type Group No. setting by wireless remote controller for centralized control1. When in the normal mode, push “ ” button for 4 seconds or more, and operation thenenters the “field set mode.”2. Set mode No. “00” with “ ” button.3. Set the group No. for each group with “ ” “ ” button (advance/backward).4. Enter the selected group numbers by pushing “ ” button.5. Push “ ” button and return to the normal mode.Group No. SettingExampleCaution When turning the power supply on, the unit may often not accept any operation while "88" isdisplaying after all indications were displayed once for about 1 minute on the liquid crystaldisplay. This is not an operative fault.Centoral RemoteControllerF1 F2F1 F2 F1 F2F1 F2P1 P2RCRCRC RC RCF1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2No Remote ControllerGroup Control by Remote Contoller(autmatic unit address)1-031-001-01Main Sub1-021-04Indoor/Outdoor Outdoor/OutdoorF1 F2 F1 F2Indoor/Outdoor Outdoor/Outdoor(V0917)