Si34-603 Field SettingTest Operation 813.1.3 Simplified Remote ControllerBRC2C511. Remove the upper part of remote controller.2. When in the normal mode, press the [BS6] BUTTON () (field set), and the FIELD SETMODE is entered.3. Select the desired MODE No. with the [BS2] BUTTON () (temperature setting V) and the[BS3] BUTTON () (temperature setting W).4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have beenselected), push the [BS8] () BUTTON (unit No.) and select the INDOOR UNIT NO. to beset. (This operation is unnecessary when setting by group.)5. Push the [BS9] BUTTON () (set A) and select FIRST CODE NO.6. Push the [BS10] BUTTON () (set B) and select SECOND CODE NO.7. Push the [BS7] BUTTON () (set/cancel) once and the present settings are SET.8. Push the [BS6] BUTTON () (field set) to return to the NORMAL MODE.9. (Example) If during group setting and the time to clean air filter is set to FILTERCONTAMINATION - HEAVY, SET MODE NO. to “10”, FIRST CODE NO. to “0”, andSECOND CODE NO. to “02”.