Troubleshooting by Indication on the Remote Controller Si34-603168 Troubleshooting3.33 “L8” Outdoor Unit: Inverter Current AbnormalRemoteControllerDisplayL8ApplicableModelsRX(Y)MQ4~6PMethod ofMalfunctionDetectionMalfunction is detected by current flowing in the power transistor.MalfunctionDecisionConditionsWhen overload in the compressor is detected.SupposedCauses Compressor overload Compressor coil disconnected Defect of outdoor unit PC board (A1P)Troubleshooting(V3184)CautionBe sure to turn off power switch before connect or disconnect connector,or parts damage may be occurred.Output current checkInverteroutputvoltage checkInverter output voltageis not balanced(Normal if within ±5V). Mustbe measured whenfrequencyis stable.Compressor overloadInspection of the compressor andrefrigerant system is required.Compressor inspectionInspect according to the diagnosisprocedure for odd noises, vibrationand operating status of thecompressor.NOReplace outdoor unit PC board(A1P).YESNOReset and restart.NOThesecondarycurrent of the inverter ishigher than 24.9A,260 sec. foreach phase.Replace the compressor.NOYESCompressorinspection Thecompressor's coil isdisconnected.YESYESDisconnect the the connectionbetween the compressor andinverter. Make the powertransistor check mode settingON by service mode.After turningon again, "L8" blinksagain.