Si34-603 Troubleshooting by Remote ControllerTroubleshooting 1172.2 Self-diagnosis by Wired Remote ControllerExplanation If operation stops due to malfunction, the remote controller’s operation LED blinks, andmalfunction code is displayed. (Even if stop operation is carried out, malfunction contents aredisplayed when the inspection mode is entered.) The malfunction code enables you to tell whatkind of malfunction caused operation to stop. See page 124 for malfunction code andmalfunction contents.Note:1. Pressing the INSPECTION/TEST button will blink the check indication.2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds ormore will clear the failure history indication shown above. In this case, on the codes display,the malfunction code will blink twice and then change to “00” (=Normal), the Unit No. willchange to “0”, and the operation mode will automatically switch from check mode to normalmode (displaying the set temperature).Operation LEDON/OFF buttonMalfunction codeInspection displayInspection/Test buttonDisplay of indoor unit forwhich a malfunction hasbeen detected