Refrigerant Piping SiE33-003138 Installation Manual6.3 Connecting the Refrigerant Piping1. PipingInstallationInstallation of refrigerant piping is possible as front connection, side connection and bottom connection.Caution Be sure to use the attached pipe when carrying out piping work in the field.Separately use the optional “KHF30A30L” or “KHF30A30U” piping kit when carrying out connections forthe side and bottom on RSXYP24, 26, 28, and 30.Connect the flange on the valve on the gas side before connecting the flare nut on the valve on theliquid side.(Connecting the liquid side first will make it harder to connect the gas side.)Be sure that the local piping does not touch other pipes, the bottom panel or side panel. Especiallyfor the bottom and side connection, be sure to protect the gas piping with the provided insulation,to prevent it from coming into contact with the casing.Notes: 1. Front Connection Make sure to close the piping intake hole again after installation work. Stop valve cover2. Side Connection Use a hammer and knock out the hole. Piping kit “KHF30A30L” is required for RSXYP24,26,28 and 30.Refer the optional “KHF30A30L” or “KHF30A30U” piping kit on page 104 for more detail.1. Flange2. Flare nut3. Gas side attached pipe4. Gas side optional pipe5. Liquid side attached pipe(Field supply, in case ofRSXYP24)6. Liquid side optional pipe(Field supply, in case ofRSXYP24)7. Gas side pipe (Field supply)8. Liquid side pipe(Field supply)9. Elbow (Field supply)10.Brazing11.Knock out hole(use a hammer)181032RSXYP16,18,2018211103712981110371235RSXYP24,26,28,30101011244661 144261011Fig. 6(V0854)1. Part to cut off (Cut off the slit part.)2. Part to cut off (Cut grooves on the back side.)RSXYP16,18,201RSXYP24,26,28,302Fig. 7(V0855)Si33-003.book Page 138 Monday, June 25, 2001 9:06 AMВсе каталоги и инструкции здесь: http://splitoff.ru/tehn-doc.html