Test Operation SiE33-00386 General Information4.14 Contents of Control ModesTwenty modes consisting of combinations of the following five operation modes with temperature andoperation mode setting by remote control can be set and displayed by operation modes 0 through 19. ON/OFF control impossible by remote controlUsed when you want to turn on/off by central remote control only.(Cannot be turned on/off by remote control.) OFF control only possible by remote controlUsed when you want to turn on by central remote control only, and off by remote control only. CentralizedUsed when you want to turn on by central remote control only, and turn on/off freely by remote controlduring set time. IndividualUsed when you want to turn on/off by both central remote control and remote control. Timer operation possible by remote controlUsed when you want to turn on/off by remote control during set time and you do not want to startoperation by central remote control when time of system start is programmed.How to SelectOperation ModeWhether operation by remote control will be possible or not for turning on/off, controlling temperature orsetting operation mode is selected and decided by the operation mode given on the right edge of the tablebelow.Do not select “timer operation possible by remote control” if not using a remote control. Operation by timeris impossible in this case.∗1. Factory settingON by remotecontrol(Unified ON bycentral remotecontrol)OFF by remotecontrol(Unified OFF bycentral remotecontrol)Temperaturecontrol byremote controlOperation modesetting byremote controlOFF byremotecontrolControlmode is "1."Example↓Rejection↓Rejection↓Rejection↓Acceptance↓Acceptance (V1345)Control mode Control by remote control ControlmodeOperation OFF Temperaturecontrol OperationmodesettingUnified operation, individualoperation by central remotecontrol, or operationcontrolled by timerUnified OFF, individual stopby central remote control, ortimer stopON/OFF controlimpossible byremote controlRejection (Example) Rejection (Example) Rejection(Example)Rejection Acceptance 0Rejection 10Acceptance(Example) Acceptance(Example) 1(Example)Rejection 11OFF control onlypossible by remotecontrolAcceptance Rejection Acceptance 2Rejection 12Acceptance Acceptance 3Rejection 13Centralized Acceptance Rejection Acceptance 4Rejection 14Acceptance Acceptance 5Rejection 15Individual Acceptance Rejection Acceptance 6Rejection 16Acceptance Acceptance 7 ∗1Rejection 17Timer operationpossible by remotecontrolAcceptance(During timer at ON positiononly)Acceptance(During timer at ON positiononly)Rejection Acceptance 8Rejection 18Acceptance Acceptance 9Rejection 19Si33-003.book Page 86 Monday, June 25, 2001 9:06 AMВсе каталоги и инструкции здесь: http://splitoff.ru/tehn-doc.html