ESIE12-06 Field Setting from Outdoor Unit PCBField Setting 953.2.3 Setting Mode 2In this mode, settings for the following items can be made.Press the MODE (BS1) button for 5seconds and set to “Setting mode 2”.Press the SET (BS2) button and set theLED display to a setting item (∗1).↓Press the RETURN (BS3) button anddecide the item.Press the SET (BS2) button and set tothe setting condition you want.↓Press the RETURN (BS3) button anddecide the condition.Press the RETURN (BS3) button andset to the initial status of “Setting mode2”.∗ If you become unsure of how to proceed, push the MODE (BS1) button and return to setting mode 1.h: OFF k: ONNo.Display of setting items Display of setting conditionsSetting items LED display Setting condition LED DisplayH1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P3 Demand 2 operation bck h h h h bck bck30% Demand k h h h k h h40% Demand (factory set) k h h h h k h50% Demand k h h h h h k11 TeS Lower limit value bck h h bck h bck bck0°C k h h h h h k2°C (factory set) k h h h h k h4°C k h h h h k k6°C k h h h k h h28 Refrigerant recoverymode k h k k k h h OFF (factory setting) k h h h h h kON k h h h h k h33 TeS Lower limit value k k h h h h k0°C (factory set) k h h h h h k6°C k h h h h k h9°C k h h h h k k11°C k h h h k h h13°C k h h h k h k15°C k h h h k k h17°C k h h h k k kWeather depending controlin cooling k h h k h h h34 TcS Upper limit value k k h h h k h60°C k h h h h h k50°C k h h h h k h47°C k h h h h k k45°C k h h h k h h43°C k h h h k h kWeather depending controlin heating k h h h k k h54Weather dependingcontrol TeS Lower limitvalue A k k k h k k h9°C (factory set) k h h h h h k11°C k h h h h k h13°C k h h h h k k15°C k h h h k h h