ESIE12-06 SpecificationsSpecifications 15Notes:1. PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC2. 3 with re-charging3. See separate drawing for electrical dataPipingconnectionsLiquidQty 1Type Flare connectionOD mm 9.52GasQty 1Type Flare connectionOD mm 15.9DrainQty 5Type HoleOD mm 26PipinglengthOU - IU(Min.) m 5 (2)OU - IU(Max.) m 50 75System -Equivalent m 70 90System -Chargeless m 30Additional refrigerantcharge kg/m See installation manual 4P302555-1LeveldifferenceOU - IU(Min.) m 30OU - IU(Max.) m 0.5Heat insulation Both liquid and gas pipesDefrost method Pressure equalisingDefrost control Sensor for outdoor heat exchanger temperatureCapacitycontrol Method Inverter controlledSafetydevices Item1 High pressure switch2 Fan motor thermal protection3 FuseStandardAccessoriesItem Tie-wrapsQty 2Item Installation manualQty 1PowersupplyName Y1Phase 3N~Frequency Hz 50Voltage V 380-415VoltagerangeMin. % 10Max. % 10Current Zmax List Complies to EN61000-3-11Recommended fuses A 16 20 25WiringconnectionsFor power supply See installation manual 4P302555-1For connection with indoorPower supply intake Outdoor unit onlyOutdoor unit RZQG71L7Y1B RZQG100L7Y1B RZQG125L7Y1B RZQG140L7Y1B