Function Details ESIE12-0650 Function and Control HeatingWhen the following condition consists by mounting the adaptor for wiring PCB, the drain pumpis turned on.3.1.6 Control when the Operation Mode is Set to “Auto”Setting the operation mode to “Auto” with the remote controller, the unit is controlled regardingthe contents shown below.3.1.7 Dew Condensation Prevention Control FCQG & FCQHGWhen indoor unit humidity is high during the operation, the moving range of louvers is limited.The operation of louvers while this control is activated is as shown below. FHQGIn cooling and dry operation, the following control is carried out in order to prevent dewcondensation when the horizontal blade blows air downward.Starting condition5 min. 5 sec.Drain pumpFloat switchONOFFOFFON-7 -6 -5 -4 -3 -2 -1 ±0 +1 +2 +3 +4 +5 +6-7 -6 -5 -4 -3 -2 -1 ±0 +1 +2 +3 +4 +5 +6Thermo.ONThermo.OFFThermo.ONThermo.OFF(Suction air temperature - Set temperature by remote controller) ˚C(Suction air temperature - Set temperature by remote controller) ˚CDisplay switchHeating→CoolingDisplay switchCooling→HeatingAuto coolingAuto heatingDew Condensation PreventionControlSetting of louvers Cancelled ActivatedP0 P0 P1P1 P1 P1P2 P2 P2P3 P3 P3P4 P4 P4Swing P0~P4 P1~P4& ( • Horizontal blade is set to downward flow (P3 or P4)• Cooling operation (compressor operation) continues for 30 minutes.Dew condensation preventioncontrol is activated.Dew condensation preventioncontrol is cancelled.Relative humidity is highRelative humidity is lowPosition of louvers(when viewed from horizontal direction)P0P1P2P3P4Indoor unitAIR