10 RS8GV202 © Danfoss 2016-06 AK-LM 340Common data for modulesSupply voltage 24 V d.c./a.c. +/- 20%Power consumption AK-__ (controller) 8 VAAK-XM 101, 102, 103, 107 2 VAAK-XM 204, 205, 208 5 VAAnalog inputs Pt 1000 ohm /0°C Resolution: 0.1°CAccuracy: +/- 0.5°C+/- 0.5°C between -50°C and +50°C+/- 1°C between -100°C and -50°C+/- 1°C between +50°C and +130°CPressure transmitter type AKS 32R / AKS2050/ AKS 32 (1-5 V)Resolution:1 mVAccuracy +/- 10 mVMax. connection of 5 pressure transmitters on one moduleOther pressure transmitter:Ratiometric signalMin. and max. pressure must be setMin and max. voltage must be setVoltage signal 0-10 VContact function (On/Off ) On at R < 20 ohmOff at R > 2K ohm(Gold -plated contacts not necessary)On/off supply voltage inputs Low voltage0 / 80 V a.c./d.c.Off: U < 2 VOn: U > 10 VHigh voltage0 / 260 V a.c.Off: U < 24 VOn: U > 80 VRelay outputsSPDTAC-1 (ohmic) 4 AAC-15 (inductive) 3 AU Min. 24 VMax. 230 VLow and high voltage must not be connected to the sameoutput groupSolid state outputs Can be used for loads that are cut in andout frequently, e.g. :rail heat, fans and AKV valveMax. 240 V a.c. , Min. 48 V a.c.Max. 0.5 A,Leak < 1 mAMax. 1 AKVAmbient temperature During transport -40 to 70°CDuring operation -20 to 55°C ,0 to 95% RH (non condensing)No shock influences / vibrationsEnclosure Material PC / ABSDensity IP10 , VBG 4Mounting For mounting on panel wall or DIN railWeight with screw terminals Modules in100- / 200- / controller-series Ca. 200 g / 500 g / 600 gApprovals EU low voltage directive and EMC require-ments are complied withLVD tested according to EN 60730EMC testedImmunity according to EN 61000-6-2Emission according to EN 61000-6-3UL 873, UL file number: E166834 for XM modulesUL file number: E31024 for LM modulesThe mentioned data applies to all modules.If data is specific, this is mentioned together with the module in question.Capacitive loadThe relays cannot be used for the direct connection of capacitive loads such as LEDsand on/off control of EC motors.All loads with a switch mode power supply must be connected with a suitable con-tactor or similar.