AK-LM 340 RS8GV202 © Danfoss 2016-06 59We have not used this function in ourexample. The image is included for guidanceonly.The name of the function may be xx andfurther down in the display the alarm textsmay be entered.Pressostat functions1. Go to Configuration menu2. Select Pressostats3. PressostatsConfiguration - continued3 - PressostatsThe general pressostats can be used for pressostatfunctions with relay output.The function can be connected to alarm limits andalarm texts.For each pressostat set / readout• Name• Which of the sensors is used• Actual pressure.Pressure reading on the sensor connected to thepressure switch• Used relay outputDefine whether a relay is to be used for this pres-sure switch function• Actual stateActual status on the pressostat outlet• Cut out pressureCut-out value for the pressostat• Cut in pressureCut-in value for the pressostat• Cut out delay• Cut in delay• High alarm limitHigh alarm limit• Alarm delay highTime delay for high alarm• Alarm text highIndicate alarm text for the high alarm• Low alarm limitLow alarm limit• Alarm delay lowTime delay for low alarm• Alarm text lowIndicate alarm text for low alarm