AK-LM 340 RS8GV202 © Danfoss 2016-06 75Check of connections1.Go to Configuration menu2. Select I/O status and manual3. Check Digital OutputsPress the +-button to go on to the next page4. Check Digital InputsPress the +-button to go on to the next page5. Check Analog inputsBefore the control is started we check that all inputs and outputs havebeen connected as expected.This controls requires that the setup is lockedBy means of the manual control of each output it can be checkedwhether the output has been correctly connected.AUTO The output is controlled by the controllerMAN OFF The output is forced to pos. OFFMAN ON The output is forced to pos ONActivate the various functions (the door switch and the main switch).Check that the controller registers the activation – i.e. whether the ON/OFF value is changed in the last column.Check the other digital inputs in the same way.Check that all sensors show sensible values.In our case we have no value. This may be due to the following:• The sensor has not been connected.• The sensor is short-circuited/interrupted• The point or module number has not been set up correctly.• The configuration is not locked.