3.17 Parameters: 16-** Data Readouts3.17.1 16-0* General Status16-00 Control WordRange: Function:0 N/A* [0 - 65535 N/A] View the control word sent from theadjustable frequency drive via the serialcommunication port in hex code.16-01 Reference [Unit]Range: Function:0.000 Reference-FeedbackUnit *[-999999.000 -999999.000ReferenceFeed-backUnit]View the presentreference value appliedon impulse or analogbasis in the unitresulting from theconfiguration selected in1-00 Configuration Mode(Hz, Nm or RPM).16-02 Reference %Range: Function:0.0 % * [-200.0 - 200.0%]View the total reference. The totalreference is the sum of digital, analog,preset, bus, and freeze references, pluscatch-up and slow-down.16-03 Status WordRange: Function:0 N/A* [0 - 65535 N/A] View the status word sent from theadjustable frequency drive via the serialcommunication port in hex code.16-05 Main Actual Value [%]Range: Function:0.00 %* [-100.00 - 100.00%]View the two-byte word sent withthe status word to the bus masterreporting the main actual value.16-09 Custom ReadoutRange: Function:0.00 CustomRea-doutUnit*[0.00 - 0.00CustomRea-doutUnit]View the value of customreadout from 0-30 Unit forUser-defined Readout to0-32 Custom Readout MaxValue3.17.2 16-1* Motor Status16-10 Power [kW]Range: Function:0.00kW *[0.00 -10000.00kW]Displays motor power in kW. The valueshown is calculated on the basis of theactual motor voltage and motor current.The value is filtered, and therefore approx.30 ms may pass from when an input valuechanges to when the data readout valueschange. The resolution of readout value onserial communication bus is in 10 W steps.16-11 Power [hp]Range: Function:0.00hp*[0.00 -10000.00 hp]View the motor power in HP. The valueshown is calculated on the basis of theactual motor voltage and motor current.The value is filtered, and therefore approx-imately 30 ms may pass from when aninput value changes to when the datareadout values change.16-12 Motor voltageRange: Function:0.0 V * [0.0 - 6000.0 V] View the motor voltage, a calculatedvalue used for controlling the motor.16-13 FrequencyRange: Function:0.0 Hz* [0.0 - 6500.0 Hz] View the motor frequency, withoutresonance dampening.16-14 Motor CurrentRange: Function:0.00 A * [0.00 -10000.00 A]View the motor current measured as amean value, IRMS. The value is filtered,and thus approximately 30 ms may passfrom when an input value changes towhen the data readout values change.16-15 Frequency [%]Range: Function:0.00 % * [-100.00 -100.00 %]View a two-byte word reporting the actualmotor frequency (without resonancedampening) as a percentage (scale 0000–4000 Hex) of 4-19 Max Output Frequency.Set 9-16 PCD Read Configuration index 1 tosend it with the status word instead of theMAV.Parameter Descriptions FC 300 Programming Guide3-132 MG.33.MA.22 - VLT® is a registered Danfoss trademark3