30Connection Examples:Setup ChangeSelection of setup using terminals 32 and 33.See the descriptions of parameters 300 through 307.Parameter 306 = Selection of Setup, lsbParameter 307 = Selection of Setup, msbParameter 002 = Multi Setup003 Copying of Setups (Setup Copy)Value:✭ No copying (NO COPY) [0]Copy active Setup to Setup 1(COPY TO SETUP 1) [1]Copy active Setup to Setup 2(COPY TO SETUP 2) [2]Copy active Setup to Setup 3(COPY TO SETUP 3) [3]Copy active Setup to Setup 4(COPY TO SETUP 4) [4]Copy active Setup to all (COPY TO ALL) [5]Function:A copy is made from the active setup selected in parameter 002, ActiveSetup, to the setup or setups selected in parameter 003, Copying ofSetups.NOTECopying is only possible when drive is stopped.Description of choice:The copying starts when the required copying function has beenselected and the OK key has been pressed.The display indicates when copying is in progress.004 LCP Copy (LCP COPY)Value:✭ No copying (NO COPY) [0]Upload all parameters(UPLOAD ALL PARAMET.) [1]Download all parameters(DOWNLOAD ALL PARAM.) [2]Download power-independent parameters(DOWNLOAD SIZE INDEP.) [3]Function:Parameter 004, LCP Copy, is used to copy all parameter setups to orfrom the Local Control Panel (LCP). This can be used to store abackup copy of all parameters in the LCP or to copy all setups fromone drive to another.Description of choice:Select Upload all parameters if all parameter values are to be copiedfrom the drive to the LCP.Select Download all parameters if all parameter values are to becopied from the LCP to the drive on which the control panel has beenmounted.Select Download power-independent parameters if only the power-independent parameters are to be downloaded. This allows theparameters from one drive to be easily copied to another drive of adifferent size.NOTECopying is only possible when drive is stopped.Setup of User-Defined ReadoutParameter 005, Maximum Value of User-Defined Readout, andParameter 006, Unit for User-Defined Readout, allow users to designtheir own readout which can be seen if the User-Defined Readout hasbeen selected as one of the displayed meters. The range is set inparameter 005, Maximum Value of User-Defined Readout and the unitis determined in parameter 006, Unit for User-Defined Readout. Thechoice of unit determines whether the relationship between the outputfrequency and the readout is a linear, square or cubed. Unitsrepresenting rates (RPM, CFM, GPM, etc.) are linear. Units represent-ing pressure (PSI, in. wg., etc.) are square. Units representing power(HP, kW, etc.) are cubed.✭ Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.