6.3.8 Analog In/Out 6-**Par. No.#Parameter description Default value 4 set-up Change duringoperationConver-sion indexType6-0* Analog I/O Mode6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint86-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint86-1* Analog Input 536-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 Int166-11 Terminal 53 High Voltage 10.00 V All set-ups TRUE -2 Int166-12 Terminal 53 Low Current 4.00 mA All set-ups TRUE -5 Int166-13 Terminal 53 High Current 20.00 mA All set-ups TRUE -5 Int166-14 Terminal 53 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int326-15Terminal 53 High Ref./Feedb.Value ExpressionLimit All set-ups TRUE -3 Int326-16 Terminal 53 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint166-17 Terminal 53 Live Zero [1] Enabled All set-ups TRUE - Uint86-2* Analog Input 546-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 Int166-21 Terminal 54 High Voltage 10.00 V All set-ups TRUE -2 Int166-22 Terminal 54 Low Current 4.00 mA All set-ups TRUE -5 Int166-23 Terminal 54 High Current 20.00 mA All set-ups TRUE -5 Int166-24 Terminal 54 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int326-25Terminal 54 High Ref./Feedb.Value 100.000 N/A All set-ups TRUE -3 Int326-26 Terminal 54 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint166-27 Terminal 54 Live Zero [1] Enabled All set-ups TRUE - Uint86-3* Analog Input X30/116-30 Terminal X30/11 Low Voltage 0.07 V All set-ups TRUE -2 Int166-31 Terminal X30/11 High Voltage 10.00 V All set-ups TRUE -2 Int166-34Term. X30/11 Low Ref./Feedb.Value 0.000 N/A All set-ups TRUE -3 Int326-35Term. X30/11 High Ref./Feedb.Value 100.000 N/A All set-ups TRUE -3 Int326-36 Term. X30/11 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint166-37 Term. X30/11 Live Zero [1] Enabled All set-ups TRUE - Uint86-4* Analog Input X30/126-40 Terminal X30/12 Low Voltage 0.07 V All set-ups TRUE -2 Int166-41 Terminal X30/12 High Voltage 10.00 V All set-ups TRUE -2 Int166-44Term. X30/12 Low Ref./Feedb.Value 0.000 N/A All set-ups TRUE -3 Int326-45Term. X30/12 High Ref./Feedb.Value 100.000 N/A All set-ups TRUE -3 Int326-46 Term. X30/12 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint166-47 Term. X30/12 Live Zero [1] Enabled All set-ups TRUE - Uint8How to program the adjustab... VLT AQUA 12-Pulse High Power Instruction Manual6-44 MG.20.Y1.22 - VLT® is a registered Danfoss trademark66