Manual initialization procedure1. Remove power to the unit and wait for thedisplay to turn off.2. Press and hold [Status], [Main Menu], and [OK] atthe same time while applying power to the unit(approximately 5 s or until audible click and fanstarts).Factory default parameter settings are restored duringstart-up. This may take slightly longer than normal.Manual initialization does not reset the followingadjustable frequency drive information:• 15-00 Operating hours• 15-03 Power-ups• 15-04 Over Temps• 15-05 Over Volts5.4 Basic Programming5.4.1 Commissioning with SmartStartThe SmartStart wizard enables fast configuration of basicmotor and application parameters.• At first power-up or after initialization of theadjustable frequency drive, SmartStart starts byitself.• Follow on-screen instructions to completecommissioning of the adjustable frequency drive.Always reactivate SmartStart by selecting QuickMenu Q4 - SmartStart.• For commissioning without use of the SmartStartwizard, refer to chapter 5.4.2 Commissioning via[Main Menu] or the Programming Guide.NOTICE!Motor data are required for the SmartStart set-up. Therequired data are normally available on the motornameplate.The SmartStart configures the adjustable frequency drive inthree phases, each consisting of several steps, seeTable 5.6.Phase Comment1 Basic Programming Program, e.g., motor data2 Application SectionSelect and programappropriate application:• Single pump/motor• Motor alternation• Basic cascade control• Master/follower3 Water and Pump Features Go to water and pumpdedicated parametersTable 5.6 SmartStart, Set-up in three Phases5.4.2 Commissioning via [Main Menu]Recommended parameter settings are intended for start-up and checkout purposes. Application settings may vary.Enter data with power ON, but before operating theadjustable frequency drive.1. Press [Main Menu] on the LCP.2. Press the navigation keys to scroll to parametergroup 0-** Operation/Display and press [OK].130BP066.101107 RPM0 - ** Operation/Display1 - ** Load/Motor2 - ** Brakes3 - ** Reference / Ramps3.84 A 1 (1)Main MenuFigure 5.2 Main MenuCommissioning VLT® AQUA Drive FC 20228 Danfoss A/S © 10/2014 All rights reserved. MG20MA2255