Mains Supply 3 x 380 - 480 VACP500 P560 P630 P710Typical Shaft output at 400V [kW] 500 560 630 710Typical Shaft output at 460V [HP] 650 750 900 1000Enclosure IP21, 54 F17 F17 F17 F17Output currentContinuous(at 400 V) [A] 880 990 1120 1260Intermittent (60 sec over-load)(at 400 V) [A]968 1089 1232 1386Continuous(at 460/ 480 V) [A] 780 890 1050 1160Intermittent (60 sec over-load)(at 460/ 480 V) [A]858 979 1155 1276Continuous KVA(at 400 V) [KVA] 610 686 776 873Continuous KVA(at 460 V) [KVA] 621 709 837 924Max. input currentContinuous(at 400 V ) [A] 857 964 1090 1227Continuous (at 460/ 480 V)[A] 759 867 1022 1129Max. cable size,motor[mm2 (AWG2))]8x150(8x300 mcm)Max. cable size,mains F1/F2 [mm2 (AWG2))]8x240(8x500 mcm)Max. cable size,mains F3/F4 [mm2 (AWG2))]8x456(8x900 mcm)Max. cable size, loadshar-ing [mm2 (AWG2))]4x120(4x250 mcm)Max. cable size, brake[mm2 (AWG2))4x185(4x350 mcm)Max. external pre-fuses [A]1 1600 2000Est. motor power loss atrated max. load [W]4) , 400V, F1 & F210647 12338 13201 15436Est. motor power loss atrated max. load [W] 4) ,460 V, F1 & F29414 11006 12353 14041Max added losses of A1RFI, Circuit Breaker or Dis-connect, & Contactor, F3 &F4963 1054 1093 1230Max Panel Options Losses 400Weight,enclosure IP21, IP 54 [kg] 2009Weight Drivesection [kg] 1004Weight Filtersection [kg] 1005Efficiency4) 0.96Output frequency 0-600 HzHeatsink overtemp. trip 95 °CPower card ambient trip 68 °C1) For type of fuse see sectionFuses.2) American Wire Gauge.3) Measured using 5 m screened motor cables at rated load and rated frequency.4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety in voltage and cableconditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power lossin the frequency converter and opposite. If the switching frequency is increased comed to the default setting, the power losses may rise sig-nificantly.LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses.(Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).VLT AQUA Low Harmonic Drive Operating In-structions 8 General SpecificationsMG.20.T1.02 - VLT® is a registered Danfoss trademark 1678