4.4 Field Installation of Options4.4.1 Installation of Input Plate OptionsThis section is for the field installation of input option kits available for frequency converters in all D and E frames.Do not attempt to remove RFI filters from input plates. Damage may occur to RFI filters if they are removed from the input plate.NB!Where RFI filters are available, there are two different type of RFI filters depending on the input plate combination and the RFI filtersinterchangeable. Field installable kits in certain cases are the same for all voltages.380 - 480 V380 - 500 VFuses Disconnect Fuses RFI RFI Fuses RFI DisconnectFusesD11 176F8443 176F8441 176F8445 176F8449 176F8447E7 FC 102/ 202: 315 kWFC 302: 250 kW176F0253 176F0255 176F0257 176F0258 176F0260FC 102/ 202: 355-450 kWFC 302: 315-400 kW176F0254 176F0256 176F0257 176F0259 176F0262NB!For further information, please see the Instruction Sheet,175R57954.4.2 Installation of Mains Shield for Frequency ConvertersThe mains shield is for installation with D and E frames and satisfy BG-4 requirements.Ordering numbers:D frames: 176F0799E frames: 176F1851NB!For further information, please see the Instruction Sheet,175R59234.5 Frame size F Panel OptionsSpace Heaters and ThermostatMounted on the cabinet interior of frame size F frequency converters, space heaters controlled via automatic thermostat help control humidity inside theenclosure, extending the lifetime of drive components in damp environments. The thermostat default settings turn on the heaters at 10° C (50° F) andturn them off at 15.6° C (60° F).Cabinet Light with Power OutletA light mounted on the cabinet interior of frame size F frequency converters increase visibility during servicing and maintenance. The housing the lightincludes a power outlet for temporarily powering tools or other devices, available in two voltages:• 230V, 50Hz, 2.5A, CE/ENEC• 120V, 60Hz, 5A, UL/cULTransformer Tap Setup4 How to InstallVLT AQUA Low Harmonic Drive Operating In-structions40 MG.20.T1.02 - VLT® is a registered Danfoss trademark4