Par. 14-22Operation Mode initialises all except:Par. 14-50RFI FilterPar. 8-30ProtocolPar. 8-31AddressPar. 8-32Baud RatePar. 8-35Minimum Response DelayPar. 8-36Max Response DelayPar. 8-37Maximum Inter-Char DelayPar. 15-00Operating Hours to par. 15-05Over Volt'sPar. 15-20Historic Log: Event to par. 15-22Historic Log: TimePar. 15-30Alarm Log: Error Code to par. 15-32Alarm Log: TimeNB!Parameters selected in par. 0-25My Personal Menu, will stay present, with default factory setting.Manual initialisationNB!When carrying out manual initialisation, serial communication, RFI filter settings and fault log settings are reset.Removes parameters selected in par. 0-25My Personal Menu.1. Disconnect from mains and wait until the display turns off.2a. Press [Status] - [Main Menu] - [OK] at the same time whilepower up for Graphical LCP (GLCP)2b. Press [Menu] while power up for LCP 101, Numerical Display3. Release the keys after 5 s4. The frequency converter is now programmed according todefault settingsThis parameter initialises all except:Par. 15-00Operating HoursPar. 15-03Power Up'sPar. 15-04Over Temp'sPar. 15-05Over Volt's5.1.11 RS-485 Bus ConnectionBoth filter portion and frequency converter can be connected to a con-troller (or master) together with other loads using the RS-485 standardinterface. Terminal 68 is connected to the P signal (TX+, RX+), whileterminal 69 is connected to the N signal (TX-,RX-).Always use parallel connections for the Low harmonic Drive to ensure thatboth filter and drive part is connected..Illustration 5.4: Connection example.In order to avoid potential equalizing currents in the screen, earth the cable screen via terminal 61, which is connected to the frame via an RC-link.Bus terminationThe RS-485 bus must be terminated by a resistor network at both ends. If the drive is the first or the last device in the RS-485 loop, set the switch S801on the control card for ON.For more information, see the paragraphSwitches S201, S202, and S801.VLT AQUA Low Harmonic Drive Operating In-structions 5 How to Operate the Low Harmonic DriveMG.20.T1.02 - VLT® is a registered Danfoss trademark 775