WARNING/ALARM 27, Brake chopper faultThe brake transistor is monitored during operation and if it short-circuits,the brake function disconnects and issues a warning. The frequency con-verter is still able to run, but since the brake transistor has short-circuited,substantial power is transmitted to the brake resistor, even if it is inactive.Turn off the frequency converter and remove the brake resistor.This alarm/ warning could also occur should the brake resistor overheat.Terminal 104 to 106 are available as brake resistor. Klixon inputs, seesection Brake Resistor Temperature Switch.WARNING/ALARM 28, Brake check failedBrake resistor fault: the brake resistor is not connected or not working.Check parameter 2-15, Brake Check.ALARM 29, Heatsink tempThe maximum temperature of the heatsink has been exceeded. The tem-perature fault will not be reset until the temperature falls below a definedheatsink temperature. The trip and reset point are different based on thedrive power size.Troubleshooting:Ambient temperature too high.Too long motor cable.Incorrect clearance above and below the drive.Dirty heatsink.Blocked air flow around the drive.Damaged heatsink fan.For the D, E, and F Frame Drives, this alarm is based on the temperaturemeasured by the heatsink sensor mounted inside the IGBT modules. Forthe F Frame drives, this alarm can also be caused by the thermal sensorin the Rectifier module.Troubleshooting:Check fan resistance.Check soft charge fuses.IGBT thermal sensor.ALARM 30, Motor phase U missingMotor phase U between the frequency converter and the motor is miss-ing.Turn off the frequency converter and check motor phase U.ALARM 31, Motor phase V missingMotor phase V between the frequency converter and the motor is missing.Turn off the frequency converter and check motor phase V.ALARM 32, Motor phase W missingMotor phase W between the frequency converter and the motor is miss-ing.Turn off the frequency converter and check motor phase W.ALARM 33, Inrush faultToo many power-ups have occurred within a short time period. Let unitcool to operating temperature.WARNING/ALARM 34, Fieldbus communication faultThe fieldbus on the communication option card is not working.WARNING/ALARM 35, Out of frequency range:This warning is active if the output frequency has reached the high limit(set in parameter 4-53) or low limit (set in parameter 4-52). InProcessControl, Closed Loop (parameter 1-00) this warning is displayed.WARNING/ALARM 36, Mains failureThis warning/alarm is only active if the supply voltage to the frequencyconverter is lost and par. 14-10Mains Failure is NOT set to OFF. Checkthe fuses to the frequency converterALARM 38, Internal faultIt may be necessary to contact your Danfoss supplier. Some typical alarmmessages:0 Serial port cannot be initialized. Serious hardware failure256-258 Power EEPROM data is defect or too old512 Control board EEPROM data is defect or too old513 Communication time out reading EEPROM data514 Communication time out reading EEPROM data515 Application Orientated Control cannot recognize the EE-PROM data516 Cannot write to the EEPROM because a write commandis on progress517 Write command is under time out518 Failure in the EEPROM519 Missing or invalid Barcode data in EEPROM783 Parameter value outside of min/max limits1024-1279A cantelegram that has to be sent, couldn't be sent1281 Digital Signal Processor flash timeout1282 Power micro software version mismatch1283 Power EEPROM data version mismatch1284 Cannot read Digital Signal Processor software version1299 Option SW in slot A is too old1300 Option SW in slot B is too old1301 Option SW in slot C0 is too old1302 Option SW in slot C1 is too old1315 Option SW in slot A is not supported (not allowed)1316 Option SW in slot B is not supported (not allowed)1317 Option SW in slot C0 is not supported (not allowed)1318 Option SW in slot C1 is not supported (not allowed)1379 Option A did not respond when calculating Platform Ver-sion.1380 Option B did not respond when calculating Platform Ver-sion.1381 Option C0 did not respond when calculating PlatformVersion.1382 Option C1 did not respond when calculating PlatformVersion.1536 An exception in the Application Orientated Control isregistered. Debug information written in LCP9 TroubleshootingVLT AQUA Low Harmonic Drive Operating In-structions174 MG.20.T1.02 - VLT® is a registered Danfoss trademark9