Normal overload 110% for 1 minuteMains Supply 3 x 380 - 480 VACFrequency converterTypical Shaft Output [kW]P37K37P45K45P55K55P75K75P90K90Typical Shaft Output [HP] at 460 V 50 60 75 100 125EncapsulationIP 20IP 21 C1 C1 C1 C2 C2IP 55 C1 C1 C1 C2 C2IP 66 C1 C1 C1 C2 C2Output currentContinuous(3 x 380-440 V) [A] 73 90 106 147 177Intermittent(3 x 380-440 V) [A] 80.3 99 117 162 195Continuous(3 x 440-480 V) [A] 65 80 105 130 160Intermittent(3 x 440-480 V) [A] 71.5 88 116 143 176Continuous kVA(400 V AC) [kVA] 50.6 62.4 73.4 102 123Continuous kVA(460 V AC) [kVA] 51.8 63.7 83.7 104 128Max. cable size:(mains, motor, brake)[[mm2/AWG] 50/1/0 104 128Max. input currentContinuous(3 x 380-440 V ) [A] 66 82 96 133 161Intermittent(3 x 380-440 V ) [A] 72.6 90.2 106 146 177Continuous(3 x 440-480 V) [A] 59 73 95 118 145Intermittent(3 x 440-480 V) [A] 64.9 80.3 105 130 160Max. pre-fuses1) [A] 100 125 160 250 250EnvironmentEstimated power lossat rated max. load [W] 4) 698 843 1083 1384 1474Weight enclosure IP20 [kg]Weight enclosure IP 21 [kg] 45 45 45 65 65Weight enclosure IP 55 [kg] 45 45 45 65 65Weight enclosure IP 66 [kg] 45 45 45 - -Efficiency 4) 0.98 0.98 0.98 0.98 0.991. For type of fuse see sectionFuses2. American Wire Gauge3. Measured using 5 m screened motor cables at rated load and rated frequency4. The typical power loss is at normal load conditions and expected to be within +/- 15%(tolerance relates to variety in voltage and cable conditions).Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiencymotors will also add to the power loss in the frequency converter and vice versa.If the switching frequency is raised from nominal the power losses may rise significantly.LCP and typical control card power consumptions are included. Further options and cus-tomer load may add up to 30W to the losses. (Though typically only 4W extra for a fullyloaded control card, or options for slot A or slot B, each).Although measurements are made with state of the art equipment, some measurementinaccuracy must be allowed for (+/- 5%).9. SpecificationsVLT ® AQUA DriveOperating Instructions130 MG.20.M2.02 - VLT ® is a registered Danfoss trademark9