7. How to programme the frequency converter7.1. How to programme7.1.1. Parameter Set-UpGroup Title Function0- Operation / Display Parameters related to the fundamental functions of the frequency con-verter, function of the LCP buttons and configuration of the LCP display.1- Load / Motor Parameter group for motor settings.2- Brakes Parameter group for setting brake features in the frequency converter.3- Reference / Ramps Parameters for reference handling, definitions of limitations, and con-figuration of the reaction of the frequency converter to changes.4- Limits / Warnings Parameter group for configuring limits and warnings.5- Digital In/Out Parameter group for configuring the digital inputs and outputs.6- Analog In/Out Parameter group for configuration of the analog inputs and outputs.8- Communication and Options Parameter group for configuring communications and options.9- Profibus Parameter group for Profibus-specific parameters.10- DeviceNet Fieldbus Parameter group for DeviceNet-specific parameters.11- LonWorks Parameter group for LonWorks parameters13- Smart Logic Parameter group for Smart Logic Control14- Special Functions Parameter group for configuring special frequency converter functions.15- Drive Information Parameter group containing frequency converter information such asoperating data, hardware configuration and software versions.16- Data Readouts Parameter group for data read-outs, e.g. actual references, voltages,control, alarm, warning and status words.18- Info and Readouts This parameter group contains the last 10 Preventive Maintenance logs.20- Drive Closed Loop This parameter group is used for configuring the closed loop PID Con-troller that controls the output frequency of the unit.21- Extended Closed Loop Parameters for configuring the three Extended Closed Loop PID Con-trollers.22- Application Functions These parameters monitor water applications.23- Time-based Functions These parameters are for actions needed to be performed on a daily orweekly basis, e.g. different references for working hours/non-workinghours.25- Basic Cascade Controller Func-tionsParameters for configuring the Basic Cascade Controller for sequencecontrol of multiple pumps.26- Analog I/0 Option MCB 109 Parameters for configuring the Analog I/0 Option MCB 109.27- Extended Cascade Control Parameters for configuring the Extended Cascade Control.29- Water Application Functions Parameters for setting water specific functions.31- Bypass Option Parameters for configuring the Bypass OptionTable 7.1: Parameter GroupsParameter descriptions and selections are displayed on the graphic (GLCP) or numeric (NLCP) inthe display area. (See Section 5 for details.) Access the parameters by pressing the [QuickMenu] or [Main Menu] key on the control panel. The quick menu is used primarily for commis-sioning the unit at start-up by providing those parameters necessary to start operation. The mainmenu provides access to all parameters for detailed application programming.All digital input/output and analog input/output terminals are multifunctional. All terminals havefactory default functions suitable for the majority of water applications but if other special func-tions are required, they must be programmed in parameter group 5 or 6.7.1.2. Quick Menu ModeThe GLCP provides access to all parameters listed under the Quick Menus. The NLCP only providesaccess to the Quick Setup parameters. To set parameters using the [Quick Menu] button:Pressing [Quick Menu] the list indicates the different areas contained in the Quick menu.VLT ® AQUA DriveOperating Instructions 7. How to programme the frequency converterMG.20.M2.02 - VLT ® is a registered Danfoss trademark 577