20-81 PID Normal/Inverse ControlOption: Function:[0] * Normal[1] InverseNormal [0] causes the frequency converter’s output frequencyto decrease when the feedback is greater than the setpoint ref-erence. This is common for pressure-controlled supply fan andpump applications.Inverse [1] causes the frequency converter’s output frequencyto increase when the feedback is greater than the setpoint ref-erence. This is common for temperature-controlled cooling ap-plications, such as cooling towers.7.1.11. Initialisation to Default SettingsInitialise the frequency converter to default settings in two ways:Recommended initialisation (via par. 14-22)1. Select par. 14-222. Press [OK]3. Select “Initialisation”4. Press [OK]5. Cut off the mains supply and waituntil the display turns off.6. Reconnect the mains supply - thefrequency converter is now reset.7. Change par. 14-22 back toNormalOperation.NB!Keeps parameters selected inPersonal Menu with default factory setting.Par. 14-22 initialises all except:14-50RFI 18-30Protocol8-31Address8-32Baud Rate8-35Minimum Response Delay8-36Max Response Delay8-37Max Inter-char Delay15-00 to 15-05 Operating data15-20 to 15-22 Historic log15-30 to 15-32 Fault logManual initialisation1. Disconnect from mains and wait untilthe display turns off.2a. Press [Status] - [Main Menu] - [OK]at the same time while power up forLCP 102, Graphical Display2b. Press [Menu] while power up for LCP101, Numerical Display3. Release the keys after 5 s.4. The frequency converter is now pro-grammed according to default set-tings.This procedure initialises all except:15-00Operating Hours15-03Power-up's15-04Over temp's15-05Over volt's7. How to programme the frequency converterVLT ® AQUA DriveOperating Instructions84 MG.20.M2.02 - VLT ® is a registered Danfoss trademark7