4.1.2 ConversionThe various attributes of each parameter are displayed infactory setting. Parameter values are transferred as wholenumbers only. Conversion factors are therefore used totransfer decimals.4-12 Motor Speed Low Limit [Hz] has a conversion factor of0.1. To preset the minimum frequency to 10 Hz, transferthe value 100. A conversion factor of 0.1 means that thevalue transferred is multiplied by 0.1. The value 100 istherefore read as 10.0.Examples:0 s ⇒ conversion index 00.00 s ⇒ conversion index -20 ms ⇒ conversion index -30.00 ms ⇒ conversion index -5Conversion index Conversion factor1007574676 10000005 1000004 100003 10002 1001 100 1-1 0.1-2 0.01-3 0.001-4 0.0001-5 0.00001-6 0.000001-7 0.0000001Table 4.2 Conversion Table4.1.3 Active/Inactive Parameters in Different Drive Control Modes+ = active- = not active1-10 Motor Construction AC motor PM Non salient Motor1-01 Motor ControlPrincipleU/fmode VVCplus FluxsensorlessFlux w/motorfeedbackU/fmode VVCplus FluxsensorlessFlux w/motorfeedback0-** Operation and Display (allparameters) + + + +1-00 Configuration Mode[0] Speed Open Loop + + + -[1] Speed Closed Loop - + - +[2] Torque - - - +[3] Process + + + -[4] Torque Open Loop - + - -[5] Wobble + + + +[6] Surface Winder + + + -[7] Ext. PID Open Loop + + + -[8] Ext. PID Closed Loop - + - +1-02 Flux Motor FeedbackSource - - - +1-03 Torque Characteristics - +see 1, 2, 3)+see 1, 3, 4)+see 1, 3, 4)1-04 Overload Mode + + + + + + +1-05 Local Mode Configuration + + + + + + +1-06 Clockwise Direction + + + + + + +1-20 Motor Power [kW](Par. 023 = International) + + + +1-21 Motor Power [HP](Par. 023 = US) + + + +Parameter Lists VLT® AutomationDrive FC 301/302 Programming GuideMG33MH02 - Rev. 2013-09-30 1614 4