2.1.10 Changing DataThe procedure for changing data is the same in the Quickmenu and the Main menu mode. Press [OK] to change theselected parameter.The procedure for changing data depends on whether theselected parameter represents a numerical data value or atext value.2.1.11 Changing a Text ValueIf the selected parameter is a text value, change the textvalue with the [▲] [▼] keys.Place the cursor on the value to save and press [OK].130BP068.10740RPM0 -01 Language[0] English10.64 A 1 [1]0-0*Basic SettingsIllustration 2.16 Changing a Text Value2.1.12 ChangingIf the selected parameter represents a numeric data value,change the selected data value by means of the [◀] [▶]navigation keys as well as the [▲] [▼] navigation keys. Press[◀] [▶] keys to move the cursor horizontally.130BP069.101- 6*113 RPM 1.78 A 1(1)Load depen. setting1 - 60 Low speed loadcompensation100%Illustration 2.17 Changing a Data ValuePress [▲] [▼] keys to change the data value. [▲] increasesthe data value, and [▼] decreases the data value. Place thecursor on the value to save and press [OK].130BP070.101 - 60 Low speed loadcompensation1 0%Load depen. setting 1- 6*729RPM 6.21A 1(1)6Illustration 2.18 Saving a Data Value2.1.13 Infinitely Variable Change ofNumeric Data ValueIf the selected parameter represents a numeric data value,select a digit with [◀] [▶].130BP073.10635 RPM1 - 71 Start Delay00.0s0.44 A 1 (1)1- 7*Start AdjustmentsIllustration 2.19 Selecting a DigitChange the selected digit infinitely variably with [▲] [▼].The selected digit is indicated by the cursor. Place thecursor on the digit to save and press [OK].130BP072.10957RPM1-71 High starting torque time0. s11.58A 1 (1)1-7*Start Adjustments4Illustration 2.20 Saving2.1.14 Value, Step-by-StepCertain parameters can be changed step by step orinfinitely varying. This applies to 1-20 Motor Power [kW],1-22 Motor Voltage and 1-23 Motor Frequency.The parameters are changed both as a group of numericdata values and as numeric data values infinitely varying.2.1.15 Read-out and Programming ofIndexed ParametersParameters are indexed when placed in a rolling stack.15-30 Fault Log: Error Code to 15-32 Alarm Log: Time containa fault log which can be read out. Select a parameter,press [OK], and use [▲] [▼] to scroll through the value log.Use 3-10 Preset Reference as another example:How to Programme VLT® AutomationDrive FC 301/302 Programming GuideMG33MH02 - Rev. 2013-09-30 192 2