2.6 Restoring Default SettingsSelect initialisation mode according to the requirement forretaining parameter settings.Recommended initialisation (viaparameter 14-22 Operation Mode).Use this method to perform initialisation without resettingcommunication settings.1. Select parameter 14-22 Operation Mode.2. Press [OK].3. Select Initialisation and Press [OK].4. Cut off the mains supply and wait until thedisplay turns off.5. Reconnect the mains supply6. The frequency converter is now reset, with theexception of the following parameters:8-30 Protocolparameter 8-31 Addressparameter 8-32 Baud Rateparameter 8-33 Parity / Stop Bitsparameter 8-35 Minimum Response Delayparameter 8-36 Maximum Response Delayparameter 8-70 BACnet Device Instanceparameter 8-72 MS/TP Max Mastersparameter 8-73 MS/TP Max Info Framesparameter 8-74 "I am" Serviceparameter 8-75 Intialisation Passwordparameter 15-00 Operating hours toparameter 15-05 Over Volt'sparameter 15-03 Power Up'sparameter 15-04 Over Temp'sparameter 15-05 Over Volt'sparameter 15-30 Alarm Log: Error Code15-4* Drive identification parametersparameter 1-06 Clockwise Direction2-finger initialisationUse this method to perform initialisation, including reset ofcommunication settings.1. Power off the frequency converter.2. Press [OK] and [Menu] simultaneously.3. Power up the frequency converter while stillpressing the keys above for 10 s.4. The frequency converter is now reset, with theexception of the following parameters:parameter 15-00 Operating hoursparameter 15-03 Power Up'sparameter 15-04 Over Temp'sparameter 15-05 Over Volt's15-4* Drive identification parametersThe alarm AL80 appears as confirmation that parametersare initialised. Press [Reset].Programming VLT® DriveMotor FCP 106 and FCM 106 Programming GuideMG03N102 - Rev. 2013-12-02 152 2