5-51 Term. 29 High FrequencyRange: Function:32000 Hz* [5 - 32000Hz]Enter the high frequency limitcorresponding to the high motor shaftspeed (i.e. high reference value) in5-53 Term. 29 High Ref./Feedb. Value.5-52 Term. 29 Low Ref./Feedb. ValueRange: Function:0 * [-4999 -4999 ]Enter the low reference value limit for themotor shaft speed [RPM]. This is also thelowest feedback value, see also5-13 Terminal 29 Digital Input = [32] PulseInput).5-53 Term. 29 High Ref./Feedb. ValueRange: Function:50 * [-4999 -4999 ]Enter the high reference value [RPM] forthe motor shaft speed and the highfeedback value, see also 5-13 Terminal 29Digital Input = [32] Pulse Input).4.6.6 5-9* Bus ControlledThis parameter group selects digital and relay outputs viaa fieldbus setting.5-90 Digital & Relay Bus ControlRange: Function:0* [0 - 0xFFFFFFFF ] This parameter holds the state of thedigital outputs and relays that iscontrolled by bus.A logical '1' indicates that the output ishigh or active.A logical '0' indicates that the output islow or inactive.Bit 0-3 ReservedBit 4 Relay 1 output terminalBit 5 Relay 2 output terminalBit 6-23 ReservedBit 24 Terminal 42 Digital OutputBit 25 Terminal 45 Digital OutputBit 26-31 ReservedTable 4.6 Bit Functions4.7 Main Menu - Analog In/Out - Group 6Parameter group for setting up the analog I/O configu-ration and the digital output. The frequency converter isequipped with 2 analog inputs: Terminal 53 and 54. Theanalog inputs can freely be allocated to either voltage(0-10 V) or current input (0/4-20 mA)4.7.1 6-0* Analog I/O Mode6-00 Live Zero Timeout TimeRange: Function:10 s* [1 - 99 s] Enter the time-out time.6-01 Live Zero Timeout FunctionOption: Function:Select the time-out function. The function setin parameter 6-01 Live Zero Timeout Function isactivated, if the input signal on terminal 53 or54 is below 50% of the value inparameter 6-10 Terminal 53 Low Voltage,parameter 6-12 Terminal 53 Low Current,parameter 6-20 Terminal 54 Low Voltage orparameter 6-22 Terminal 54 Low Current for atime period defined in parameter 6-00 LiveZero Timeout Time.[0] * Off[1] Freezeoutput[2] Stop[3] Jogging[4] Max. speed[5] Stop andtripRef./Feedback[RPM]Analog inputHigh Ref./Feedb. Value'Low Ref./Feedb. Value''Low Voltage'or'Low Current''High Voltage'or'High Current'130BA038.131 V 5 V 10 V30060090012001500[V]150Par 6-xxPar 6-xxPar 6-xxPar 6-xxIllustration 4.12 Live Zero Timeout Function4.7.2 6-1* Analog Input 53Parameters for configuring the scaling and limits foranalog input 53 (terminal 53).Parameters VLT® DriveMotor FCP 106 and FCM 106 Programming GuideMG03N102 - Rev. 2013-12-02 594 4