14-64 Dead Time Compensation Zero Current LevelFor a long motor cable, set this parameter to [0] to minimize themotor-torque ripple.Option: Function:[0] * Disabled[1] Enabled14-65 Speed Derate Dead Time CompensationRange: Function:Expres-sionlimit(50)Hz*[Expres-sionlimit(20) -Expres-sionlimit(1000) Hz]Deadtime compensationlevel is reduced linearly inrelation to outputfrequency. The maximumlevel is set by 14-07 DeadTime Compensation Level.The minimum outputfrequency level is defined in14-65 Speed Derate DeadTime Compensation.4.10.7 14-9* Fault SettingsFault Customisation Settings14-90 Fault LevelUse this parameter to customise fault levels. Setting theparameter value may change 1-73 Flying Start.Option: Function:[3] * Trip lock[4] Trip with delayed reset[5] Flystart4.11 Main Menu - Drive Information - Group15Parameter group containing frequency converterinformation such as operating data, hardware configu-ration and software versions.4.11.1 15-0* Operating Data15-00 Operating hoursRange: Function:0 h* [0 - 0x7fffffff. h] View how many hours the frequencyconverter has run. The value is savedwhen the frequency converter is turnedoff.15-01 Running HoursRange: Function:0 h* [0 -0x7fffffff. h]View how many hours the motor has run.Reset the counter in parameter 15-07 ResetRunning Hours Counter. The value is savedwhen the frequency converter is turned off.15-02 kWh CounterRange: Function:0 kWh* [0 -65535kWh]View the output power of the frequencyconverter in kWh as a mean value over 1hour. Reset the counter inparameter 15-06 Reset kWh Counter.15-03 Power Up'sRange: Function:0* [0 - 2147483647 ] View the number of times the frequencyconverter has been powered up.15-04 Over Temp'sRange: Function:0* [0 - 65535 ] View the number of frequency convertertemperature faults which have occurred.15-05 Over Volt'sRange: Function:0* [0 - 65535 ] View the number of frequency converterovervoltages which have occurred.15-06 Reset kWh CounterOption: Function:NOTICEPres [OK] to reset.[0] * Do not reset[1] Reset counter Select [1] Reset and press [OK] to reset thekWh counter to zero (seeparameter 15-02 kWh Counter).15-07 Reset Running Hours CounterOption: Function:[0] * Do not reset[1] Reset counter Select [1] Reset counter and press [OK] toreset Running Hours counter(parameter 15-01 Running Hours) to zero (seealso parameter 15-01 Running Hours).4.11.2 15-3* Alarm LogParameters in this group are array parameters, where up to10 fault logs can be viewed. [0] is the most recent loggeddata, and [9] the oldest. Error codes, values, and timestamp can be viewed for all logged data.15-30 Alarm Log: Error CodeRange: Function:0* [0 - 255 ] View the error code and look up its meaning inchapter 5 Diagnostics and Troubleshooting.Parameters VLT® DriveMotor FCP 106 and FCM 106 Programming GuideMG03N102 - Rev. 2013-12-02 794 4