4 Parameters4.1 Main Menu - Operation and Display -Group 0Parameters related to the fundamental functions of thefrequency converter, function of the LCP keys and configu-ration of the LCP display.4.1.1 0-0* Basic Settings0-01 LanguageOption: Function:Defines the language to be used in the display.[0] * English[1] Deutsch[2] Francais[3] Dansk[4] Spanish[5] Italiano[28] Bras.port[255] No Text0-03 Regional SettingsOption: Function:NOTICEThis parameter cannot be adjusted whilethe motor is running.To meet the needs for different default settingsin different parts of the world,parameter 0-03 Regional Settings is implementedin the frequency converter. The selected settinginfluences the default setting of the motornominal frequency.[0] Interna-tionalSets default value of parameter 1-23 MotorFrequency [50 Hz].[1] NorthAmericaSets the default value of parameter 1-23 MotorFrequency to 60 Hz.0-04 Operating State at Power-upOption: Function:Select the operating mode upon reconnectionof the frequency converter to mains voltageafter power down when operating in Hand(local) mode.[0] * Resume Resumes operation of the frequency convertermaintaining the same local reference and thesame start/stop condition (applied by [HandOn]/[Off] on the LCP or Hand Start via a digital0-04 Operating State at Power-upOption: Function:input as before the frequency converter waspowered down.[1] Forcedstop,ref=oldUses saved reference [1] to stop the frequencyconverter but at the same time retain the localspeed reference in memory before poweringdown. After mains voltage is reconnected andafter receiving a start command (pressing [HandOn] key or using her Hand Start command via adigital input) the frequency converter restartsand operates at the retained speed reference.0-06 GridTypeOption: Function:Select the grid type of the supplyvoltage/frequency.NOTICENot all choices are supported in allpower sizes.IT grid is a supply mains, where thereare no connections to ground.Adjust the position of the RFI switch tomatch the grid type (refer toVLT®DriveMotor FCP 106 and FCM 106Operating Instructions)Delta is a supply mains where thesecondary part of the transformer isdelta connected and one phase isconnected to ground.[10] 380-440V/50Hz/IT-grid[11] 380-440V/50Hz/Delta[12] 380-440V/50Hz[20] 440-480V/50Hz/IT-grid[21] 440-480V/50Hz/Delta[22] 440-480V/50Hz[110] 380-440V/60Hz/IT-grid[111] 380-440V/60Hz/Delta[112] 380-440V/60Hz[120] 440-480V/60Hz/IT-grid[121] 440-480V/60Hz/DeltaParameters VLT® DriveMotor FCP 106 and FCM 106 Programming Guide34 MG03N102 - Rev. 2013-12-0244