4) Measured using 16.5 ft. [5 m] shielded motor cables at rated load and rated frequency.5) Wiring terminals on N132, N160, and N315 adjustable frequency drives cannot receive cables one size larger.8.1.2 Line Power Supply 3 x 525–690 V ACN75K N90K N110 N132 N160 N200Normal Overload =110%current for 60 secondsNO NO NO NO NO NOTypical Shaft output at 550 V[kW] 55 75 90 110 132 160Typical Shaft output at 575 V[hp] 75 100 125 150 200 250Typical Shaft output at 690 V[kW] 75 90 110 132 160 200Enclosure IP20 D3h D3h D3h D3h D3h D4hEnclosure IP21 D1h D1h D1h D1h D1h D2hEnclosure IP54 D1h D1h D1h D1h D1h D2hOutput currentContinuous (at 550 V) [A] 90 113 137 162 201 253Intermittent (60 s overload) (at550 V) [A] 99 124 151 178 221 278Continuous (at 575/690 V) [A] 86 108 131 155 192 242Intermittent (60 s overload) (at575/690 V) [kVA] 95 119 144 171 211 266Continuous kVA (at 550 V)[kVA] 86 108 131 154 191 241Continuous kVA (at 575 V)[kVA] 86 108 130 154 191 241Continuous kVA (at 690 V)[kVA] 103 129 157 185 229 289Max. Input currentContinuous (at 550 V) [A] 89 110 130 158 198 245Continuous (at 575 V) [A] 85 106 124 151 189 234Continuous (at 690 V) [A] 87 109 128 155 197 240Max. cable size: line power,motor, brake, and load share(mm2/AWG2))2x95 (2x3/0)Max. external electrical fuses[A] 160 315 315 315 350 350Estimated power loss at 575 V[W] 3) 1,161 1,426 1,739 2,099 2,646 3,071Estimated power loss at 690 V[W]3) 1,203 1,476 1,796 2,165 2,738 3,172Weight, enclosures IP20, IP21,IP54 kg [lbs] 62 [135]Efficiency 4) 0.98Output frequency [Hz] 0–590Heatsink overtemp. trip [°C] 110Power card ambient trip [°C] 75Table 8.3 Line Power Supply 3 x 525–690 V ACGeneral Specifications and ... Design Guide206 Danfoss A/S © Rev. 2014-01-13 All rights reserved. MG16C12288