A S S e r i e s H a r d wa r e Ma n u a l1 2 - 2 4_12Errorcode Description CPUstatusERROR LED indicator statusON BlinkingfastBlinkingnormallyBlinkingslowly OFF8105The contents of the downloaded program areincorrect.The program syntax is incorrect.Continue V8106The contents of the downloaded program areincorrect.The length of the execution code exceeds the limit.Continue V8107The contents of the downloaded program areincorrect.The length of the source code exceeds the limit.Continue V8000-8FFFErrors occur between software and PLC. Continue V12.4.2 Error Codes and LED Indicators for Analog/Temperature ModulesError code DescriptionERROR LED indicator statusA D /D A /A ↔DERROR16#1605 Hardware failure OFF ON16#1607 The external voltage is abnormal. OFF ON16#1608 The factory calibration or the CJC is abnormal. OFF ON16#1801*1 The external voltage is abnormal. OFF Blinking16#1802*1 Hardware failure OFF Blinking16#1804*1 The factory calibration is abnormal. RUN: BlinkingSTOP: OFF Blinking16#1807*1 The CJC is abnormal. OFF Blinking16#1808 The signal received by channel 1 exceeds the range ofanalog inputs (temperature).RUN: BlinkingSTOP: OFF Blinking16#1809 The signal received by channel 2 exceeds the range ofanalog inputs (temperature).16#180A The signal received by channel 3 exceeds the range ofanalog inputs (temperature).16#180B The signal received by channel 4 exceeds the range ofanalog inputs (temperature).16#180C The signal received by channel 5 exceeds the range ofanalog inputs (temperature).16#180D The signal received by channel 6 exceeds the range ofanalog inputs (temperature).16#180E The signal received by channel 7 exceeds the range ofanalog inputs (temperature).16#180F The signal received by channel 8 exceeds the range ofanalog inputs (temperature).*1: The following errors are specified as warnings to ensure the CPU module can still run even when the warnings are