C h a p t e r 1 2 Tr o u b l e s h o o t i n g1 2 - 2 512_triggered by its AIO modules. You can set up HWCONFIG to have the following first 4 error codes appear as errors whenthey occur.12.4.3 Error Codes and LED Indicators for Load Cell Module AS02LCError code DescriptionERROR LED indicator statusA D ERROR16#1605 Hardware failure (the diver board included) OFF ON16#1607 The external voltage is abnormal. OFF ON16#1801*1 The external voltage is abnormal. OFF Blinking16#1802*1 Hardware failure OFF Blinking16#1807*1 Diver board failure OFF Blinking16#1808 The signal received by channel 1 exceeds the range ofanalog inputs or the SEN voltage is abnormal.RUN: BlinkingSTOP: OFF Blinking16#1809 The signal received by channel 1 exceeds the weight limit.16#180A The factory calibration in channel 1 is incorrect.16#180B The signal received by channel 2 exceeds the range ofanalog inputs or the SEN voltage is abnormal.16#180C The signal received by channel 2 exceeds the weight limit.16#180D The factory calibration in channel 2 is incorrect.*1: The following errors are specified as warnings to ensure the CPU module can still run even when the warnings aretriggered by its AIO modules. You can set up HWCONFIG to have the following first 3 error codes appear as errors whenthey occur.12.4.4 Error Codes and LED Indicators for Module AS00SCM as aCommunication ModuleError Code DescriptionERROR LED indicator statusON Blinking16#1605 Hardware failure V16#1606 The setting of the function card is incorrect. V16#1802 Incorrect parameters V16#1803 Communication timeout V16#1804 The setting of the UD Link is incorrect. V12.4.5 Error Codes and LED Indicators for Module AS00SCM as a RemoteModuleError Code DescriptionERROR LED indicator statusON Blinking Blinkingfast16#1301 Hardware failure V16#1302 The setting of the function card is incorrect. V