Chapter 11 Summary of Parameter SettingsCP200011-1202 Digital Input / Output ParametersPr. Explanation Settings FactorySetting02-00 2-wire / 3-wire operation control0: 2-wire mode 1, power on for operation control1: 2-wire mode 2, power on for operation control2: 3-wire, power on for operation control002-01 Multi-function input command 1 (MI1) 0: No function 102-02 Multi-function input command 2 (MI2) 1: Multi-stage speed command 1 202-03 Multi-function input command 3 (MI3) 2: Multi-stage speed command 2 302-04 Multi-function input command 4 (MI4) 3: Multi-stage speed command 3 402-05 Multi-function input command 5 (MI5) 4: Multi-stage speed command 4 002-06 Multi-function input command 6 (MI6) 5: Reset 002-07 Multi-function input command 7 (MI7) 6: JOG command (By KPC-CC01 or external 002-08 Multi-function input command 8 (MI8) control) 002-26 Input terminal of I/O extension card(MI10)7: Acceleration / deceleration speed inhibit8: The 1 st, 2 nd acceleration / deceleration time 002-27 Input terminal of I/O extension card(MI11)selection9: The 3 rd, 4 th acceleration / deceleration time 002-28 Input terminal of I/O extension card(MI12)selection10: EF input (Pr. 07-20) 002-29 Input terminal of I/O extension card(MI13)11: B.B input from external (Base Block)12: Output stop 002-30 Input terminal of I/O extension card(MI14)13: Cancel the setting of auto accel. / decel.time 002-31 Input terminal of I/O extension card(MI15)14: Switch between motor 1 and motor 215: Operation speed command from AVI1 016: Operation speed command from ACI17: Operation speed command from AVI218: Emergency stop (Pr. 07-20)19: Digital up command20: Digital down command21: PID function disabled22: Clear counter23: Input the counter value (MI6)24: FWD JOG command25: REV JOG command28: Emergency stop (EF1)29: Signal confirmation for Y-connection30: Signal confirmation for ᇞ-connection