Chapter 11 Summary of Parameter SettingsCP200011-4212 PUMP ParametersPr. Explanation Settings FactorySetting12-00 Cycle Control0: Disable1: Time cycle2: Qualitative cycle3: Qualitative control4: Time cycle + Qualitative cycle5: Time cycle + Qualitative control012-01 Number of Motors to beconnected 1~8 112-02 Operating time of each motor(minutes) 0~65500 min. 012-03Delay Time due to theAcceleration (or the Increment )at Motor Switching (seconds)0.0~3600.0 sec. 1.012-04Delay Time due to theDeceleration ( or the Decrement)at Motor Switching (seconds)0.0~3600.0 sec. 1.0 12-05Delay time while fixed quantitycirculation at Motor Switching(seconds)0.0~3600.0 sec. 10.0 12-06Frequency when switchingmotors at fixed quantitycirculation (Hz)0.00~599.00Hz 60.012-07Action to do when FixedQuantity Circulation breaksdown0: Turn off all output1: Motors powered by mains electricity continues tooperate0 12-08 Frequency when stoppingauxiliary motor (Hz) 0.00~599.00Hz 0.00