OPERATIONEaton 9155 UPS (8–15 kVA) User's Guide 164201553 Rev G (www.eaton.com/powerquality) 59User SettingsThe following table displays the options that can be changed by the user.NOTE Changes to the output voltage or frequency options should be made before turning on the UPS;otherwise, the changes do not take effect.Table 9. User SettingsDescription Available Settings Default SettingSet Date and Time Set MonthDate: mm/dd/yyyyTime: 24:0001/01/200300:00Display Contrast Adjust contrast with up/down arrow buttons ModerateChange Language Select Language: Elegir idioma EnglishRelay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4]Setup: [empty] [On Battery] [Summary Alarm] [On Bypass] [UPS ok][custom]Alarm 1: emptyX-Slots (1 or 2)#1: UPS ok#2: On Bypass#3: Summary Alarm#4: On BatterySignal Inputs [empty] [Logic](see “Programmable Signal Inputs” on page 56)Serial Port Config Port: [X-Slot-1] [X-Slot-2/Serv]Speed: [19200] [9600] [2400] [1200]19200Parallel Operation Settings Refer to the Eaton 9155 Parallel UPS (8–15 kVA) User's Guide.Modem Config Modem Installation Set Modem Call Events Event #0Call modem: noSet Modem Init String ATZ0Set Modem Call Command NoneSet Modem Communication Password NoneStart Screen Eaton logoMimic screenEaton logoUser Password Enabled/DisabledIf Enabled is selected, the password is USER.DisabledAudible Alarms Normal Sound/Disabled Normal SoundBattery Charging ABM cycling/constant ABM cyclingAutomatic Battery Tests Enabled/DisabledEnabled automatically runs the battery test once a month.EnabledFull Power Battery Test Enabled/Disabled EnabledNumber of Battery Strings 0 through 22(see “Configuring the UPS for EBMs” on page 64)2 strings for UPS-32 models4 strings for UPS-64 modelsBattery Capacity 1 through 65535 watts per cell 34 W/cellBattery Low Alarm Level 1.750 through 1.950 volts per cell 1.880 V/cell