SPECIFICATIONSEaton 9155 UPS (8–15 kVA) User's Guide 164201553 Rev G (www.eaton.com/powerquality)74Table 13. Dimensions and WeightsDimensions (H x W x D) Weight2-High UPS 32.2” 12” 32” (81 30 81 cm) 352 lb (160 kg)3-High UPS-32 47.8” 12” 32” (121.5 30 81 cm) 550 lb (250 kg)3-High UPS-64 47.8” 12” 32” (121.5 30 81 cm) 590 lb (268 kg)2-High EBM 32.2” 12” 30.3” (81 30 77 cm) 480 lb (218 kg)3-High EBM 47.8” 12” 30.3” (121.5 30 77 cm) 710 lb (322 kg)PDM (rear UPS mount) 16.5” 12” 7” (42 30 17.8 cm) 25 lb (11 kg)MBM (rear UPS mount) 16.5” 12” 7” (42 30 17.8 cm) 18 lb (8 kg)Table 14. Environmental and Safety SpecificationsOperating Temperature 50°F to 104°F (10°C to 40°C)Optimal battery performance: 77°F (25°C)Transit Temperature -13°F to 131°F (-25°C to 55°C)Storage Temperature 32°F to 77°F (0°C to 25°C)Recommended battery storage: 15°C to 25°C (59°F to 77°F)Ventilation Front air intake, forced air, two fans, positive pressurization,temperature UPS-monitoredAltitude 9,843 ft (3,000m) operating without derating32,810 ft (10,000m) during transportationRelative Humidity 5–95% noncondensingHeat Dissipation 5582 BTU/hr maximum online5294 BTU/hr maximum on batteryAudible Noise <56 dBA at 1 meter distance, typical loads<62 dBA for heavy load, high ambient or high altitude, on batterySurge Suppression ANSI C62.41 Category B3Safety Conformance NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3;EN 55022 Class A (CISPR22 Class A) and IEC 60950; IEC 62040-1-1Agency Markings cULus, cUL, CE, NOM-NYCEEMC (Class A) IEC 62040-2, FCC Part 15, ICES-003, VCCI