Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F www.eaton.com/powerquality 9Chapter 3 UPS SetupThis chapter describes:l Equipment inspectionl Floor loading and clearancesl Removing and replacing the cabinet doorsl Unloading the cabinet(s)The instructions are intended for the chief operator/system supervisor, electrical consultants, and installationelectricians. Local regulations and electrical code must be followed during the UPS installation.Inspecting the EquipmentIf any equipment has been damaged during shipment, keep the shipping and packing materials for the carrieror place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claimfor concealed damage.To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt ofthe equipment; 2) Send a copy of the damage claim within 15 days to your service representative.Note: Check the battery recharge date on the packaging label. If the date has expired and the batteries werenever recharged, do not use the UPS. Contact your service representative.Floor LoadingWhen planning the installation, consider the UPS weight for floor loading. The strength of the installationsurface must be adequate for point and distributed loadings. The approximate weights are shown in thefollowing table.ClearancesThe following clearances are recommended for the Eaton 9355 UPS:Standard Model Floor LoadingsEaton 9355 Maximum Weight Point Loading20 kVA UPS 1160 lb (526 kg) 290 lb/in2 (20 kg/cm2 )30 kVA UPS 1160 lb (526 kg) 290 lb/in2 (20 kg/cm2 )EBC 36 1160 lb (526 kg) 290 lb/in2 (20 kg/cm2 )EBC 72 2060 lb (934 kg) 515 lb/in2 (36 kg/cm2 )Options Cabinet withSingle Transformer535 lb (243 kg) 134 lb/in 2 (9.4 kg/cm 2)Options Cabinet withDual Transformer792 lb (360 kg) 198 lb/in2 (13.9 kg/cm2 )Options Cabinet with MBS only 205 lb (93 kg) 51 lb/in2 (3.6 kg/cm2 )From Front of Cabinet 36" (91.4 cm) working spaceFrom Back of Cabinet 6" (15.2 cm)From Right of Cabinet Refer to local codes for right side service access [minimum 36" (91.4 cm)]