Operation70 Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F www.eaton.com/powerqualityThe following table shows the basic menu structure.User SettingsThe following table displays the options that can be changed by the user.Note: Changes to the output voltage or frequency options should be made before turning on the UPS;otherwise, the changes do not take effect.Table 6. Menu Map for Display FunctionsMain Menu Submenu Display Information or Menu FunctionUPS Status UPS off / System normal / UPS supporting load / UPS on battery / UPS on bypass / Active alarmlist / Battery statusFor parallel systems: System normal / Battery floating UPS in Parallel mode / Parallel UnitNumber x / Units on CAN Bus / Units on loadEvent Log Displays up to 127 events and alarmsMeasurements Parallel System(parallel UPSs only)Voltage [by unit] / Voltage [Parallel total] / Output Voltage: L-N / Output Voltage L-L / OutputCurrent / Output Frequency / Output PowerOutput L-N and L-L / Current / Frequency / Power (kW/kVA/pf)Battery Voltage / Current / RuntimeInput L-N and L-L / Current / FrequencyBypass L-N and L-L / FrequencyControl Go to Bypass Mode Transfers the UPS to internal Bypass modeWhen this command is active, the option changes to Go to Normal Mode.Start Battery Test Initiates a battery testDisplay Test Four different selectable tests for the front panel functions: the LEDs cycle through, the alarmbeep sounds, the backlight turns off and on, and the pixels scroll through to test the LCD.Settings User Settings See Table 7 for detail.Service Settings This screen is password-protected.Identification UPS Type / Part Number / Serial Number / Firmware / Display / CAN BridgeTurn UPS ON/OFF ON and OFF OptionsTable 7. User SettingsDescription Available Settings Default SettingSet Date and Time Set MonthDate: mm/dd/yyyyTime: 24:0001/01/200300:00Display Contrast Adjust contrast with up/down arrow buttons ModerateChange Language Select Language: Elegir idioma Choisir la langue EnglishSet Nominal Output Voltage Output:[120V/208V] [127V/220V]120V/208VRelay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4]Setup: [Battery Low] [On Battery] [On Bypass] [UPS ok][custom] [empty]Alarm 1: emptyX-Slots (1 or 2)#1: UPS ok#2: On Bypass#3: Summary Alarm#4: On Battery