34 Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 03Figure 10. Battery Life ResetControlGo to bypassLoad segmentsUPS firmwareConnectivity testFunctions resetMeasurementsControlSettingsEvent logFault logIdentificationRegister productMenu100 % 100 %Online modePress the Enter Buttonto advance the menu2.4kW3.0kVA19min1 EBMEfficiency: 94%Reset battery lifeYes NoAre you sure?Reset battery lifeDoneUPS firmwareFunctions resetReset Fault stateReset power usageBMS auto setupReset battery lifeNMC card resetReturn the UPS to Normal OperationIf the UPS internal batteries and external battery packs were replaced without powering down the UPS:1. Check the UPS front panel display for active alarms or notices. Resolve any active alarms beforecontinuing. See section 7.1 Typical Alarms and Faults . If the indicator is on, do not proceed until allalarms are clear.2. Verify that the indicator illuminates solid, indicating that the UPS is operating normally and any loadsare powered and protected. The UPS should be in normal mode. See .If the UPS internal batteries and external battery packs were replaced and the UPS was powered off:1. Verify that the internal batteries are connected. See section .2. If optional EBMs are installed, verify that the EBM are connected to the UPS. See section .3. See section for powering the UPS back to normal operation.4. If the UPS has a MBP module attached see 3.6 Detecting other Accessories for the correct startupprocedure.Battery Settings Reset