Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 03 43Table 12. Electrical Output (Continued)All Models Normal Mode Efficiency Mode Battery Mode>130% :2s>150% : shutdown after 300 msOverload warning then transfer to stop outputOutput Overload ( BypassMode )102%~110% :Overload warning110%~130% :shutdown after 5mins130%~150% :shutdown after 15s>150% :shutdown after 300msPercent is based on nominal current in bypass modeVoltage Waveform SinewaveHarmonic Distortion < 3% THDV on linear load< 5% THDV on non-linear loadTransfer Time Online Mode: 0msHigh Efficiency mode: 10ms maximum (due to loss of utility)Power Factor Up to 1.0Load Crest Ratio Up to 3:1Table 13. Electrical Output ConnectionsModel Output Connection Output Cable9PX1000IRT2U-L9PX1500IRT2U-L(4) IEC10A(2) IEC10A group 1(2) IEC10A group 2(2) IEC10A9PX2200IRT2U-L (4) IEC10A + (1) IEC16A(2) IEC10A + (1) IEC16A group 1(2) IEC10A group 2(2) IEC 10A9PX3000IRT2U-LTable 14. Environmental and SafetyCertifications IEC/EN 62040-1IEC/EN 62040-2 : Cat. C1IEC/EN 62040-3UL1778 5th editionCSA 22.2EMC ( Emissions)* CISPR22 Class BFCC part 15 Class B / ICES-003EMC (Immunity)* IEC 61000-4-2, (ESD): 8 kV Contact Discharge / 15 kV AirDischargeIEC 61000-4-3, (Radiated field): 10 V/mIEC 61000-4-4, (EFT): Power (Coupling network) 4 kV / Ethernet(Couplingclamp) 2 kVIEC 61000-4-5, (Surges): 2 kV Differentiel Mode / 4 kV CommonMode /Model Specifications