CommissioningCopyright © 2007-2012 Eaton Corporation. All Rights Reserved.IPN 997-00012-48D November 2012 95Test Test procedure AdjustmentEqualize For details see Equalize test in System Controls on page 90.Fast Charge For details see Fast Charge test in System Controls on page90.Battery Test For details see Battery Test in System Controls on page 90.In DischargeNote 3Connect load to the system.Turn off the ac supply to the rectifiers.Allow the battery to start discharging.Ensure alarm operates.Config ErrorNote 4Load incorrect configuration file.- or -Remove all rectifiers from the system.Apply an incorrect external voltage to the system:24V for a 48V system48V for a 24V systemEnsure alarm operates.User AssignedAlarmsSee User Digital Input test on page 96.Battery CurrentLimitFor details see Battery Current Limit test in SystemControls on page 90.Rectifier No Load Ensure the dc load and batteries are isolated from thesystem.Ensure alarm operates.Rectifier CurrentLimitApply a dc load to the system.Turn off rectifiers until the remaining rectifiers reach theRectifier Current Limit threshold.- or -Set the Rectifier Current Limit slightly below the existingrectifier current being delivered to the load.Ensure alarm operates.High RectifierTemperatureNote 5Unable to test.AC Phase 1/2/3 FailNote 6Turn off ac phase 1 to the power system.Ensure alarm operates.Repeat for phase 2 and phase 3.AC Phase 1/2/3VoltageNote 6Reduce the High AC Threshold below the existing acvoltage.Ensure alarm operates.Increase the Low AC Threshold above the existing acvoltage.Ensure alarm operates.AC FrequencyNote 6Change the Nominal AC Frequency setting.Change the AC Frequency Threshold.Ensure alarm operates.Engine Run OptionNote 7Change the state of the digital input with Engine Runfunction.Ensure alarm operates.