Access Power Solutions Installation and Operation Guide (APS3-300 Series)96 Copyright © 2007-2012 Eaton Corporation. All Rights Reserved.IPN 997-00012-48D November 2012Notes1 Ensure Alarm Tracking is disabled. Ensure Temperature Compensation is enabled.2 If the load is not connected to the load MCBs and if an electronic Fuse Fail detect circuits isinstalled, this test can also be performed as follows:Turn off the load MCBConnect a high impedance path >100k ) between the end load side of the MCB and theCommon Bus. (The impedance path can also be created by touching these points withyour hand.)3 Ensure the battery discharge is high enough. Allow for the recognition time.4 This alarm will be displayed if the incorrect configuration or incorrect rectifiers are used inthe system. It is not recommended that this be tested as it is very unlikely for an incorrectconfiguration to be installed after commissioning.5 This alarm is originated from the rectifier. It can only be tested by increasing the internaltemperature of the rectifier.6 These alarms are only available with the external ac metering option.7 A digital input must be configured for this test to function. See details in the SystemController Operation Handbook.Digital InputsTest Test procedure AdjustmentDigital Input 1 Change the state of the Digital input.Ensure any alarms mapped to the digital output (relay)activate.Ensure the Digital Input Alarm Name is correct.Digital Input 2 As for Digital Input 1.Digital Input 3 As for Digital Input 1.Digital Input 4 As for Digital Input 1.Digital Input 5 As for Digital Input 1.Digital Input 6 As for Digital Input 1.User AssignedDigital InputsNote 1As for Digital Input 1.Check the severity and digital output (relay) mapping iscorrect.Notes1 As the Digital Inputs can be configured for many different digital input devices, specifictests have not been detailed on this test sheet.