15Technical Data PR202-50-502-22Effective June 2017CF2000 SystemEATON www.eaton.comMicro InterfacesA range of micro interfaces modules are also available:MIU872 is a compact single zone input, soft addressed, micro-interface, incorporating integral short circuit isolators It is fullycompatible with the current range of Cooper analogue fire detec-tion panels It is suitable for interfacing a zone of up to 20 conven-tional Cooper detectors onto a Cooper analogue fire panel It willoperate with any Cooper conventional detector in configurationwith a schottky diode type baseMCIM is a compact input module used to accept input signalsfrom external equipment such as beam detectors, flow switches,valve monitor switches etc The CF6000 can be programmed toperform different actions based on the state of the input Themaximum number of input devices per loop is 200