19Technical Data PR202-50-502-22Effective June 2017CF2000 SystemEATON www.eaton.comTechnical Specification (continued)OutputsConventional sounder circuitsNumber of sounder circuits 4Total Sounder Load 1 0A (FH1204)Maximum Sounder Circuit Load 800mASounder Circuit Fuses (F1/2/3/4) 1 6A (Quick Blow)End of line resistor 6k8Fire Routing EquipmentMax Load 60mAFused (PTC2) 100mA polyswitchEnd of Line resistor 6k8Fire Protecting EquipmentMax Load 60mAFused (PTC4) 100mA polyswitchEnd of Line resistor 6k8Fault Routing equipmentMax Load 30mAFused (PTC1) 100mA polyswitchEnd of Line resistor 6k8Auxiliary RelaysThe auxiliary relays provide fused volt free change over contacts These contacts are not monitoredMax Load 24V 1AFuse (PTC5) 1 1A polyswitchAuxiliary 24V SupplyNominal Voltage 24V ±10%Fuse (PTC3) 300 mA polyswitchMaximum current 30 mAThis output is not to be used for Fire protecting equipment or Fire alarm routing EquipmentAny power taken from the alarm system will affect the standby durationRS485 Port (Mimic Repeater)This is a serial output port for driving CF2000 Repeater panels, mimics etcThis output is short circuit protectedMax Cable Length 2 KmMin Recommended cable size 1 mm² (Screened)Mechanical SpecificationWeight including batteries 10 6 KgWeight excluding batteries 5 3 KgDimensions (Standard batteries) 400 mm (L) x 320 mm (H) x 170 mm (D)Type of Material (backbox) Mild Steel (Powder Coated)Type of Material (facia) PC/ABSFlammability Rating UL 94 V0Total Number of knockouts 24Diameter of knockout 20 mmCAUTIONTERMINAL BLOCKS: DO NOT USE EXCESSIVE FORCE WHENTIGHTENING THE SCREWS ON THE TERMINAL BLOCK