77Technical Data PR202-50-502-22Effective June 2017CF2000 SystemEATON www.eaton.comMicro Input Module Wiring MCIMTo install the device1. Fit the box in position using the mounting details below2. Connect the unit according to the diagram in Figure 563. Recommended Cable Type: FIRETUF, FP200, MICCote:NNo addressing of the interface is required See control paneloperation for details There are no serviceable parts so nomaintenance procedures applyFigure 56. Standard connections MCIM1. Only connect cable screen to its adjacent earth terminal2. The end of line resistor provided must always be fitted, even ifthe input is unused3. Monitored inputs can detect open or short circuit faults