25Technical Data PR202-50-502-22Effective June 2017CF2000 SystemEATON www.eaton.comDevice input programmingFigure 5. Device Inputs dialogDevice Input ProgrammingFire Panel reports fire from deviceFault Panel reports fault from deviceReset Panel resetsSilence Silence all currently active soundersPre-Alarm Panel reports pre-alarm from deviceNon-Latching Device does not latch in alarm condition Used in conjunction with isolatesDay/Night Option enables day/night mode on compatible heat and opto-heat detectorsOptical-Heat Mode switches between heat or optoheat modeHeat Mode switches between Heat A1R and Heat CSIsolate Zone / AddressUser can define between zones or addresses to be isolated on activation of the deviceThe isolate list button enables the user to enter up to 8 unique zones or addressesIf non-latching has been enabled, isolated devices can be un-isolated as the triggered device returns to normal operationA call point keyswitch is an example for this application