76Technical Data PR202-50-502-22Effective June 2017CF2000 SystemEATON www.eaton.comMicro Zone Monitor Wiring MIU872To install the device1. Fit the box in position using the mounting details below2. Connect the unit according to the diagram in Figure 553. Recommended Cable Type: FIRETUF, FP200, MICCote:NNo addressing of the interface is required See control paneloperation for details There are no serviceable parts so nomaintenance procedures applyFigure 55. Standard connections MIU8721. This unit can only be used with Cooper FXN520 detector baseand compatible2. Only connect cable screen to its adjacent earth terminal3. The end of line resistor provided must always be fitted, even ifthe spur is unused4. Maximum spur length - See BS5839 Pt1:2001 for ZoneCoverage5. Maximum number of call points allowed is unlimited6. Detector zone end of line device is EOLM-1 (supplied)