217 Common operation of the web screensInstallation and Operating Instructions CGLine+ Web-Controller 40071860236 (E) February 2019 www.eaton.comIn the configuration menuof the two digital inputs1 , 2 the inputs can beassigned specific commandsand the two relays can beassigned conditions whenthe relay’s state changes.Configuration of the two digital inputs 3 :n Not configured: no functionn Rest order: During a mains failure (luminaires are in emergency mode), the rest mode willswitch OFF the luminaires. If mains return, the luminaires will go back in normal mode. To thenext mains failure, the luminaires switch again to emergency mode.n Activate IA mode: Activate the Increase Affordance mode in line 1, 2, 3 and/or 4.n Maintained mode OFF per line: Switches off the maintained mode luminaires of the line aslong as the input is activen Start function test: With positive pulse, starts the function test with all luminairesn Stop FT/DT: Interrupts a duration test or function test with all luminairesn External failureConfiguration of the two relay outputs 4 :n Not configured: no functionn One luminaire fault: Common fault for at least one luminairen Three consecutive luminaires failure: At least 3 consecutive luminaires in a zone are faultyn Communication fault: At least 1 luminaire has a communication faultn Battery operation: At least 1 luminaire is in battery mode, e.g. with mains failuren Function test: At least 1 luminaire is in a function testn Duration test: At least 1 luminaire is in a duration testn Charging failure: At least 1 luminaire has a battery or charge faultn Test failure: At least 1 luminaire has an FT or DT fault, e.g. nominal operating time not reached711 „Digital input/output“ configuration screen2341